Home » Products » Pipe Clamp » UL FM Approbata Pipe Sway Brace Clamp for Fire Sprinkler Support

UL FM Approbata Pipe Sway Brace Fibulae enim ignis Sprinkler Support

UTT13 UTT18 est seismica dominatio fistulae fibulae affectum (fibulatae uestrae) machinatum ad reprimendum ignem aspersorium limbum et fistulam mechanicam contra ditionem lateralem et perturbationem seismicam. Tibiae adscriptionis componentia completae disciplinae ue rationi inservit: coniuncta cum structuris affectione convenienti et bracteali elemento, plenam seismic comprehendens conventum gravitatis et statio non-structuralis componentis format.
Fibulae usui destinatur ad systemata fistulae spargentis ignis, HVAC et plumbi fistula subsidia, et mechanico-electrica (M&E) limbis ubi moderatio seismica requiritur. Propositum est institui ad normam NFPA 13 et institutiones fabricae, et apta ad incepta quae sequuntur GB 50981 (Codex Seismic Design aedificationis mechanicae et electricae systematis). Available in chalybe carbonii et ferri ductilis QT450, cum electro-galvanizato (zinc-patella) perficiendi ut vexillum et calvanizatum peractum calidum intinge roganti, et suppletur sub UL/Fm indice.
  • UTT13 UTT18

  • funditus TY

Availability:
Quantity:
facebook sharing button
Twitter sharing button
linea participatio puga
wechat sharing button
sharingin button sharing
pinterest sharing button
whatsapp sharing button
kakao sharing button
snapchat button sharing
sharethis sharing button

Product Description

UL FM Approbata Pipe Sway Brace Fibulae enim ignis Sprinkler Support

UTT13 UTT18 est seismica dominatio fistulae fibulae affectum (fibulatae uestrae) machinatum ad reprimendum ignem aspersorium limbum et fistulam mechanicam contra ditionem lateralem et perturbationem seismicam. Tibiae adscriptionis componentia completae disciplinae ue rationi inservit: coniuncta cum structuris affectione convenienti et bracteali elemento, plenam seismic comprehendens conventum gravitatis et statio non-structuralis componentis format.
Fibulae usui destinatur ad systemata fistulae spargentis ignis, HVAC et plumbi fistula subsidia, et mechanico-electrica (M&E) limbis ubi moderatio seismica requiritur. Propositum est institui ad normam NFPA 13 et institutiones fabricae, et apta ad incepta quae sequuntur GB 50981 (Codex Seismic Design aedificationis mechanicae et electricae systematis). Available in chalybe carbonii et ferri ductilis QT450, cum electro-galvanizato (zinc-patella) perficiendi ut vexillum et calvanizatum peractum calidum intinge roganti, et suppletur sub UL/Fm indice.

Clavis Commoda  
NFPA 13 & GB 50981 Compliant – Designatur ad institutionem per NFPA 13 imperare ue requisita et GB 50981 seismic designa regulas pro systematibus M&E.
UL Optio recensita / FM Approbata - Independenter probata onera ratings pro igne tutelae et limbis mechanicis comprehendendis.
Pipe amplitudo Range - Covers aspersorium fistulae Sch 10/Sch 40, GB/T 3091 et JIS G3454 fistulae ab 1' (25) usque ad 8' (200).
Robustum Load Capacity - UL maximum consilium onerant usque ad 1,370 libras (6.09 kN); FM ad 1,010 pondo (4.49 kN) onus horizontalis aestimat.
Praesidium durabile Corrosio - zinci metam Electro-galvanized ut vexillum; calida-dip galvanized praesto est summus humiditas et sub terra raedam ambitus.
Fast, Instrumentorum simplicium instruitur - Installsway cum Sch 40 1' fistulam stringens, quattuor nuces ad 40-45 N·m contractas ecclesiam perficit, laborem pro redemptoribus minuendo.

UL FM Approbata Pipe Sway Brace Fibulae enim ignis Sprinkler Support
UL FM Approbata Pipe Sway Brace Fibulae enim ignis Sprinkler Support
UL FM Approbata Pipe Sway Brace Fibulae enim ignis Sprinkler Support

Specification

UL FM Approbata Pipe Sway Brace Fibulae enim ignis Sprinkler Support

UL Maximum Design Load

Pipe Size



libras denariorum.



kN

Wt.Each

1'(25mm) Brace Pipe

libr.

kg

1

(25).

680

(3.02)

0.71

(0.35)

1¼

(32).

680

(3.02)

0.81

(0.37)

1½

(40)

680

(3.02)

0.86

(0.39)

2

(50)

680

(3.02)

0.92

(0.42)

2½

(65)

680

(3.02)

1.01

(0.46)

3

(80)

680

(3.02)

1.08

(0.49)

4

(100)

680

(3.02)

1.21

(0.55)

5

(125)

1090

(4.84)

1.37

(0.62)

6

(150)

1370

(6.09)

1.52

(0.69)

8

(219)

1370

(6.09)

1.81

(0.82)

FM Maximum Design Load

PipeSize

Horizontalis onus ratings institutionem angulus 30°-44°

Horizontalis onus ratings institutionem angulus 45°-59°

Wt.Each

1''(25mm) Brace Pipe

Ibs.

kN

Ibs.

kN

libr.

kg

2

(50)

590

(2.62)

840

(3.73)

0.92

(0.42)

2½

(65)

710

(3.15)

1010

(4.49)

1.01

(0.46)

3

(80)

540

(2.40)

770

(3.42)

1.08

(0.49)

4

(100

540

(2.40)

770

(3.42)

1.21

(0.55)

6

(150

270

(1.20)

390

(1.73)

1.52

(0.69)

8

(200

210

(0.93)

290

(1.28)

1.81

(0.82)

UL FM Approbata Pipe Sway Brace Fibulae enim ignis Sprinkler Support

UL Maximum Design Load



PipeSize



libras denariorum.



kN

Wt.Each

1''(25mm) Brace Pipe

libr.

kg

1¼

(40)

680

(3.02)

1.23

(0.56)

2

(50)

680

(3.02)

1.36

(0.62)

2½

(65)

680

(3.02)

1.45

(0.66)

3

(80)

680

(3.02)

1.54

(0.70)

4

(100)

680

(3.02)

1.76

(0.80)

5

(125)

1090

(4.84)

2.16

(0.98)

6

(150)

1370

(6.09)

2.20

(1.00)

8

(200)

1370

(6.09)

2.79

(1.27)

Testimonia

UL FM Approbata Pipe Sway Brace Fibulae enim ignis Sprinkler Support

Institutionem

UL FM Approbata Pipe Sway Brace Fibulae enim ignis Sprinkler Support

Magnitudines pro Pipe 1' ad 6' (Top Row Reference):
Positiones (Step 1): Pone corpus U-fulmen seu fibulae circa ignem aspersorium vel fistulam mechanicam ad punctum nodi designatum. Fibulae sedet ut rubor contra tibiae superficiem.
Conventus (Step 2.): virga staminea vel fibulae nexum componentia per designata foramina in fibulae collectae inserta. Obstringere initio manum nucis positio tenere.
Destringens (Step 3.): Torque nuces ad valorem determinatum fabricae clavis torques calibratis utens. Ut virga bractealis recte alignatur cum puncto structurae ancorae ne in fibulationibus flectantur accentus.
For Pipe Size 8' (Bottom Row Reference):
Component Alignment (Step 1): Diametris majoribus (8'), align duplicem fibulae habitationem vel bracket grave circa tibiam. Sera foramina perpendicularis ad fistulam axem perpenduntur.
Impetrandum (Step. 2.): Distrahentes fulmina per fibulae alta Insere flanges. Seras aequabiliter in transverso obstringere, ut pressionis uniformis distributio circa fistulam circumferentiam curet.
Connexio finalis (Step 3): Virgam seismic fibulae affigere ad ocellatum vel bracket in fibulato integrato. Cognoscere nexum esse rigidum et fibulationes circa fistulam non gyrari.

UL FM Approbata Pipe Sway Brace Fibulae enim ignis Sprinkler Support

Fibulae tibia cum tibia et aliis nexus accessoriis ut in figura patet; Accessiones UTT18 utuntur fistulae sch40 1-inch;

Nuces constrictae usque ad 40~45N·M semel quattuor nuces installantur, institutio perfecta est.

Processus productionis

UL Ferrum ductile Adnexum Nfpa 13 Sprinkler

Packaging & Shipping

UL Ferrum ductile Adnexum Nfpa 13 Sprinkler

Interiorem sarcina: Singulae fistulae fibulae in sacculo plastico refertae, deinde in capsula e cistae electronicae exportationis positae sunt.
Exterior sarcina: munitum in thymiamatis plywood, cursares cum nexibus phalangis, ad longum spatium vecturae tutum idoneum.
Shipping Methods: Mare oneraria, oneraria aerea, et expressa internationalia praesto sunt.
Shipping Portus: Qingdao Portus, Shandong, Sinis.
Duc Tempus: 7-15 dies exempla regularis, sub ordine quantitatis.

Quid elige Us

UL Ferrum ductile Adnexum Nfpa 13 Sprinkler
Previous: 
Next: 

Product Category

Contact Us
Prorsus TY Intelligent Technologia Co.,Ltd. summus tech inceptis privatis integrandi productum est consilium, investigationem et progressionem, venditiones et institutionem.

Velox Vincula

Product Category

Contact Us

Tel: +86- 13361551928
Whatsapp:
Catharina Lee:+86 15806475072
Shirley+86 19100444278
Lancey:+86 17353654218
Address: 609, No.4931 Beihai Road, Beihai Subdistrict, Kuiwen Districtus, Weifang urbs, Shandong Province Sina



Aliquam Nuntius
Contact Us
Copyright © 2025 Prorsus TY intelligentes Technologiae Co.,Ltd. All rights reserved. | Sitemap | Privacy Policy | Supported by leadong.com